Sistemas LED 24V: entender la caída de tensión y planificar la tensión mínima de entrada

24V LED Systems: Understanding Voltage Drop and Using Minimum Input Voltage
24V LED Spot Guide By TILLUME Team Updated May 2026 Reading time 12 min

In KNX or DALI based 24V constant-voltage lighting systems, voltage drop is not a luminaire defect but a planning parameter of the low-voltage DC supply. Once cables sit between the 24V power supply, controller or dimmer and the LED spot, cable length, load, wire size and circuit grouping determine the actual input voltage at the spot. What matters is the voltage at the most unfavourable spot, not just the 24V output printed on the power supply.

TILLUME 24V LED spots use an internal driver circuit and remain stable as long as the 22V minimum input voltage is not undercut. With standards-based wiring checks, central, room-based or semi-decentralized supply layouts, TILLUME 24V DC power supplies, DALI controllers and realistic cable data, voltage drop can be checked before installation instead of guessed on site.

What this article helps you decide

  • Evaluate voltage drop as a system question involving power supply position, controller position, cable length, load and wire size.
  • Compare centralized, semi-decentralized and zone-based 24V supply layouts without forcing a false either-or decision.
  • Understand the role of 22V minimum input voltage, the upper input-voltage boundary and long-term voltage reserve.
  • Avoid common mistakes: too many spots on one run, long 24V cables, weak wiring topology or blindly increasing power-supply voltage.
Guide Series

The 24V LED spot guide series

This article is part of the TILLUME guide series for modular 24V LED spot systems. Read the series in order if you want to connect buying decisions, light quality, lumen planning, Tunable White, voltage drop, dimming and KNX/DALI/Loxone integration into one coherent lighting plan.

S1. 24V LED Spot Buying Guide 2026
The big-picture decisions: 24V constant voltage, DALI, KNX and modular lighting planning.
S1-01. Tunable White LED pink tint solution
Why some Tunable White spots look pink or magenta and when a precision CCT range helps.
S1-02. CRI, Ra and R9 in LED lighting
Evaluate color rendering for wood, skin tones, food and interior materials.
S1-03. TILLUME LED Spot 4W vs 6W vs 8W
Use wattage, lumen output and current per circuit as the basis for voltage-drop planning.
S1-04. Tunable White LED Spot: CCT, Dual White and Dim to Warm
Understand CCT and Tunable White logic before planning DT8 channels.
S1-05. Current article: Voltage Drop in 24V LED Systems
Plan power supply position, controller position, cable length, wire size and minimum input voltage together.
S1-06. 24V LED Spot Dimming: DALI, KNX, PWM and Loxone
Separate dimming paths, controller channels and system integration clearly.
S1-07. 24V LED Spot Modular System & Fixture Selection
Combine TILLUME 24V LED modules with fixture housings, modular system logic and installation checks.
S1-08. 24V LED Spot with MDT KNX Actuator
Understand how KNX actuator channels, MDT components and 24V constant-voltage LED loads fit together.
S1-09. 24V LED Spot with Lunatone DALI
Plan 24V LED spot groups with DALI or DALI-2 controllers, addresses, channels and power-supply sizing.
S1-10. 24V LED Spot with Loxone
See where Loxone controllers, dimmers and 24V LED spot modules make sense in a smart-home lighting plan.

1Start from the real project: Central or decentralized 24V supply?

When planning a 24V lighting system, you rarely start with the formula. The first questions are usually practical: Where does the 24V supply begin? Where are the power supply, driver or controller located? How long will the 24V cables be? Why can individual spots at the end of a run appear dimmer?

Layout Typical setup Advantage What to check
Central 24V distribution 24V power supply, dimmer or controller sits at an accessible technical point; 24V cables then run to spots or lighting groups. Clear maintenance, simple protection and good accessibility. Longer 24V cables can increase voltage drop and cable losses.
Decentralized or zone-based supply 230V is routed closer to the lighting zone; DALI ECGs, drivers, dimmer plus PSU, zone-based 24V DC PSU or controller sit closer to the load. Shorter 24V supply and load cables, lower voltage loss and more flexible grouping. More planning for circuits, channels, protection, access, heat and service.

Voltage drop does not happen because the LED spot is defective. It happens because every cable has resistance. When current flows, part of the voltage is lost along the cable path. For planning, the actual length and load on the 24V side behind the power supply, driver or controller channel matter most.

TILLUME system logic: TILLUME LED spots are designed for 24V systems with an internal driver circuit. They tolerate cable-related input-voltage reduction within the specified operating range, provided the 22V minimum input voltage is not undercut. Voltage drop still has to be planned; the benefit is a clear lower operating boundary.

2Circuit grouping and wire size: Reduce load first, then size the cable

Do not choose a central or decentralized supply layout first and then try to make the circuits fit. Start with real spot positions, lighting groups, room zones and expected cable lengths. Then decide whether central 24V distribution, room-based or semi-decentralized planning, or a load-near position for the 24V power supply, dimmer or controller fits better. Voltage drop is one factor; access, heat, protection, documentation and cost matter too.

The strongest electrical lever is usually not a thicker cable. It is clean load distribution. Less current on one 24V run or controller channel means less voltage loss on that path. Topology also matters: star wiring or several short branches usually keep spot input voltages closer together than one long line with many tap-off points. If a continuous line is used, return both the beginning and the end of the line to the power supply or a defined feed point. This is not series wiring; the spots remain electrically parallel on 24V DC.

24V LED spot wiring topology diagram Comparison of star wiring, several short branches and a continuous line returned to the feed point. 24V wiring topology: reduce voltage-drop risk by planning For 24V systems, check star wiring or short branches first. If a continuous line is used, return both ends to the feed point. 1. Star wiring often best to evaluate first 24V PSU SpotSpotSpotSpot more similar spot voltages 2. Short branches useful for rooms or zones 24V PSU SpotSpotSpot short load paths, clear zones 3. Continuous line only with return to feed point 24V PSU return beginning + end avoid one-sided long load path
Planning question Risk if ignored Better decision
How many spots are on one circuit? High total current and larger voltage drop at the end. Split the load across several circuits or controller channels.
How long is the longest 24V run? Long cable plus high load becomes critical. Shorten runs or redesign the zone.
Which wiring topology is used? A long one-sided line creates larger differences between near and far spots. Check star wiring or short branches first; return both ends of a continuous line to the feed point.
What wire size is used? Too small a cross section increases cable loss. Use 1.5 mm² for moderate runs; evaluate 2.5 mm² for longer runs or higher load.
  1. Clarify spot positions and zones before selecting the final equipment layout.
  2. Reduce load per circuit by using fewer spots or lower total wattage per run.
  3. Evaluate wiring topology: star wiring, several short branches or a looped line with both ends returned to the feed point.
  4. Shorten cable length through different zoning or closer equipment placement.
  5. Increase wire size when length or current requires it.
  6. Check the voltage at the most unfavourable spot by calculation or later by measurement.

The formula ΔU = 2 × L × I × ρ / A is still the useful final check. For pre-planning, ask the simpler question first: is too much current flowing through too much 24V cable? For the standards background, IEC 60364-5-52 covers the selection and erection of low-voltage wiring systems and includes voltage-drop limits in Clause 525. National implementation and project details still need to be checked by the electrician or planner.

3Controller position: Central control or load-near zone control

The next planning point is the position of the DALI or KNX controller. In many projects, the controller is first imagined inside the control cabinet. That is clean and service-friendly, but it can create longer 24V load cables to the spots. Alternatively, the controller can be placed closer to a lighting zone so that the 24V cables between controller output and LED spots remain shorter.

The controller position is not only a control question. It is also a voltage-drop question, because the critical current flows on the 24V side between the controller channel and the luminaires. For Tunable White systems, the DALI Alliance identifies DT8(Tc) as the DALI colour-control type for correlated colour temperature control under IEC 62386 Part 209. That helps define the control method; it does not remove the need to size the 24V load cables correctly.

A 24V circuit with TILLUME LED spots has room between its lower and upper input boundaries. Still, 25V is a boundary value, not a preferred continuous operating target. For long-term installations, keep the highest spot voltage below that limit with reserve, for example closer to about 24.5V instead of permanently near 25V.

4Position the supply equipment: Central, decentralized or zone-based

The 24V DC power supply defines where the 24V supply begins. So the practical check is simple: how long is the path from the power supply, dimmer or controller channel to the most unfavourable spot, how high is the load and what wire size is used?

A central solution is not wrong. It is often the cleanest option when cable lengths stay short and load per circuit is limited. A decentralized or zone-based supply becomes useful with long distances, several floors, larger rooms or high loads per zone. In real projects, decentralized does not mean one driver per spot. It more often means one supply per room, zone or lighting group.

Supply equipment layout Advantage Risk / check point Planning decision
Central technical point Good maintenance, clear protection and simple overview. Longer 24V cables can increase voltage loss. Use only when cable length, load and wire size fit.
Decentralized or zone-based near room, group or load Shorter 24V cables, lower voltage drop and better zone supply. More device positions; check access, heat and protection. Useful for long runs, several floors or high zone load.
Important: A more powerful power supply alone does not solve voltage drop if too much current still flows through long or thin cables. A 24V DC power supply should also not run continuously at its nominal limit. Plan about 20% power reserve for stable long-term operation. This reserve does not replace correct cable planning. For 230V input devices with integrated DALI or dimming functions, also check compatibility with the selected 24V LED spots, control method and service concept.

5Spot selection: Check minimum input voltage and voltage-drop reserve

Only after circuit grouping, controller position and power supply position have been considered is spot selection technically complete. In a 24V circuit, wattage alone is not enough. You also need to know what input voltage actually arrives at the end of the cable and whether that value is still inside the permitted operating range.

Product type Minimum input voltage Upper input boundary Meaning
Fixed CCT Spot 6W / 8W 22V Check by series; do not plan the upper range as the continuous target. Expert series are especially relevant when cable length leads to lower input voltage.
Tunable White Spot 6W+6W / 8W+8W 22V Check by series; Master applications may benefit from slightly increased input voltage in specific projects. Check the concrete series and application; coordinate with TILLUME in borderline cases.

Between the 24V nominal system value and the 22V boundary at the spot, there is up to 2V of voltage-drop reserve. Across the full 22V to 25V input range, the theoretical window between the highest and lowest spot voltage is up to 3V. Do not spend that whole window in normal operation. For long-term installations, keep the highest spot voltage below the upper boundary with reserve, for example around 24.5V or lower.

TILLUME 24V DC power supplies can typically be adjusted at the output in the range of 23V to 27V. This can help during commissioning to compensate for small cable losses. It does not replace correct cable planning and should not make spots run permanently near the upper boundary. The practical check is not: "Can I simply turn the power supply up?" It is: "Are all spots within the permitted input-voltage range of the selected series, and is there enough reserve for continuous operation?"

If the most distant spot is below 22V, the cable design is critical. Adjust the layout by using fewer spots per circuit, a larger wire size, shorter cable runs, a different controller position or a different power supply position. If a near spot is permanently too close to the upper input boundary, the supply voltage is set too high or the layout needs to be reviewed.

See the follow-up practical article for room layouts, spot counts, cable lengths and voltage-drop calculations with TILLUME 24V LED spots, 24V DC power supplies and DALI DT8 controllers: 24V LED Spot Configuration: Examples for Power Supply, DT8 Controller and Voltage Drop.

The difference from simple 24V LED modules lies in the internal driver circuit. Simple modules without internal regulation become darker directly as voltage falls. TILLUME LED spots keep LED current stable inside their specified input-voltage range. Voltage drop still exists, but the spot can be planned against a clear operating window.

Technical boundary: The internal driver circuit does not remove voltage drop. It compensates its effects within a defined input-voltage range. If spot input voltage falls below the minimum input voltage, brightness may decrease, Tunable White color temperature may shift, dimming behaviour may become unstable and electronics may be stressed over time. TILLUME LED spots include additional protection functions such as overcurrent protection on most models, PTC current limiting on some models and softstart. These protections usually help avoid immediate damage, but they are not permission for continuous operation outside the specification.

6Layout decision: Evaluate central, semi-decentralized and decentralized supply cleanly

If you want to control voltage drop in 24V LED systems, do not decide blindly for centralized, semi-decentralized or decentralized supply. Every layout has clear advantages and real disadvantages. The right decision only appears when circuit grouping, wiring topology, wire size, controller position, 24V power supply or dimmer position and spot operating range are evaluated together.

Layout Advantage Risk When useful?
Central 24V distribution Clear maintenance, simple protection and documentation. Long 24V cables can increase voltage loss. Small to medium rooms, short cable paths, clear channel structure.
Semi-decentralized / central per room Shorter cables than fully central, fewer device positions than fully decentralized. Service, documentation and heat must be planned carefully. Rooms with several lighting groups and medium cable lengths.
Decentralized or zone-based near the load Shorter 24V cables, lower voltage drop and better zoning. More device positions; access, protection and heat dissipation must be checked. Large rooms, long cable paths, several lighting zones or floors.
  • Central supply remains useful when cable paths are short or sufficiently sized, channel structure is clear and cabinet service access is a priority. It becomes critical when many spots, high load and long 24V cables meet on the same run.
  • Semi-decentralized or room-based supply is often the realistic middle ground: not everything sits in the main cabinet, but not every device has to sit directly at each spot. Rooms, floors or lighting groups become their own planned zones.
  • Decentralized supply reduces 24V supply and load cables but needs more conscious planning of access, heat, protection and documentation. In DALI projects this may also involve a 230V input device or driver near the load, while the concrete 24V side to the TILLUME spot still has to be checked.
  • Controller position complements power supply planning; it does not replace it. Controller channels, load per channel, service access and wiring topology must be planned together.
  • Wiring topology should be chosen deliberately: star wiring, several short branches or a continuous line returned to the feed point lead to different voltage distributions.
  • Wire size and grouping should be based on the total current of the run or controller channel, not on one individual spot. Split many spots across several circuits or channels instead of forcing everything onto one run.
  • Power supply reserve should be planned at about 20% for stable long-term operation, but it does not replace correct wiring, grouping or voltage-drop calculation.
  • Input voltage range must be checked at both the most distant and nearest spot. At the farthest spot, at least 22V should arrive; the upper boundary should not be used as the preferred continuous operating point. In borderline cases, coordinate the layout with TILLUME.

7FAQ

What does minimum input voltage mean for a 24V LED spot?

It is the lower limit of the input-voltage range that the internal driver circuit can process reliably. As long as actual spot voltage does not fall below this value, the driver keeps LED current, brightness and color temperature stable.

How long can a 24V LED cable be?

There is no universal maximum length. It depends on current, wire size and the minimum input voltage of the spots. With 4 × 8W and 1.5 mm² wire, 15 meters is usually not critical. With more spots or longer cable runs, increase wire size or split the load.

What wire size makes sense for 24V LED spots?

For most residential installations with moderate cable length up to about 10m and normal spot count, 1.5 mm² is sufficient. For longer runs or many spots per run, 2.5 mm² is recommended. Always size the cable for the total current of the run or controller channel.

Why do 24V LED spots at the end of a cable get dimmer?

Voltage drop is highest at the end of a long cable. Simple LED modules without internal regulation get dimmer directly as voltage falls. TILLUME LED spots remain stable as long as voltage does not fall below the minimum input voltage.

Does an internal driver circuit remove voltage drop?

No. It does not remove voltage drop. It compensates the effect within a defined input-voltage range. The cable voltage loss still exists, but the spot can remain visually stable inside its working range.

Do 24V LED spots need a transformer or power supply?

TILLUME 24V LED spots need a 24V DC power supply and cannot be connected directly to 230V. In German everyday language, "Trafo" and "Netzteil" are often used similarly. What matters is stable 24V DC output, sufficient power reserve of about 20% and a compatible controller or dimmer.

Central or decentralized 24V supply: which is better?

Both can be right. The deciding factors are the 24V cable length behind the power supply, dimmer or controller channel, load per circuit, wire size, maintenance access, heat, protection and the measurable voltage at the most unfavourable spot.

Star wiring or long line wiring?

Star wiring or several short branches are often better when spot voltage should remain as even as possible. A long line can create larger voltage differences. The spots still remain electrically parallel on 24V DC; the question is cable topology, not series wiring.

Does the same apply to 24V LED strips?

Yes. The physics are the same: cable length, current, wire size and feed points determine voltage loss. With LED strips, voltage drop also occurs along the strip itself, so long strip sections may need additional feed points.

8What to read next?

Want to see concrete example configurations?

The next practical article shows typical rooms, spot counts, cable paths, 24V DC power supplies and DALI DT8 controllers as traceable planning examples.

Open S1-05-01 practical examples

9Decision Hub: What Should You Read Next?

A good 24V LED spot project is not decided by voltage drop alone. Use the next articles in this guide series to connect cable planning with buying decisions, light quality, Tunable White strategy, dimming and system integration.

Your Question Recommended Next Article
I want to return to the main 24V LED spot buying decisions. S1. 24V LED Spot Buying Guide 2026
I worry about pink or magenta tint in Tunable White. S1-01. Tunable White LED pink tint solution
I want to understand CRI, Ra, R9 and color rendering. S1-02. CRI, Ra and R9 in LED lighting
I do not know whether 4W, 6W or 8W is enough. S1-03. TILLUME LED Spot 4W vs 6W vs 8W
I need to distinguish CCT, Dual White, Dim to Warm and RGBW correctly. S1-04. Tunable White LED Spot: CCT, Dual White and Dim to Warm
I am planning longer 24V cable runs and voltage-drop reserve. S1-05. Current article: Voltage Drop in 24V LED Systems
I want to understand dimming, PWM, DALI, KNX and Loxone properly. S1-06. 24V LED Spot Dimming: DALI, KNX, PWM and Loxone
I want to combine LED modules and fixture housings correctly. S1-07. 24V LED Spot Modular System & Fixture Selection
I use KNX and MDT components. S1-08. 24V LED Spot with MDT KNX Actuator
I use DALI or DALI-2. S1-09. 24V LED Spot with Lunatone DALI
I use Loxone. S1-10. 24V LED Spot with Loxone
Note: This article does not replace project-specific electrical planning. Cable lengths, protection, heat, standards, device access and concrete product data must be checked in the individual project.

ARTÍCULOS RELACIONADOS