TILLUME HLG-100W-24A LED Power Supply Test Report

1, Block Diagram

2, Performance Evaluation

This session presents the test results of HLG-100W-24A LED Power Supply up to date. Overall the power supply meets the design specification.

All data was measured at 1.5M AWG16 CABLE END

Performance Highlights

  • No load standby power: below 40mW @230V
  • Max Efficiency @ 100% Load: 90.00%@115VAC & 91.20%@230VAC

Characterization Results Summary

Test Item

Test Result

1.Input Characteristics
Standby Power at no Load 22mW
Average Efficiency( 230Vac, 100% Load) 91.20%
2. Output Characteristics
Line regulation 0.5%
Load regulation 1.5%
Ripple & Noise 100mV
Over Shoot 2.6% Max
Under Shoot 2.2% Max
Dynamic test ±360mV
3. Time Sequence
Set up time <350mS
Hold up time >25mS
Rise time <150mS
Fall time <15ms

Test Equipments

Item Brand Module
AC Source  EVERFINE DPS1005-V200
Digital Power Meter EVERFINE LT-101A
Electrical Load ITECH IT8512G+
Oscilloscope Tektronix MDO32
Thermal HIKVISION K20

2,1 Input Characteristics

2,1,1 Standby Power / PF / THD

 Table.1 Standby Power Without Load

Input Voltage Specification Standby Power(mW) Vo(V)
100Vac/60Hz 150mW 20mW 24.2
115Vac/60Hz 20mW 24.2
230Vac/50Hz 30mW 24.2
264Vac/50Hz 50mW 24.2

Table.2 PF and THD with Full load

Input Voltage Specification PF Specification THD(%)
100Vac/60Hz >0.95 0.99 <20% 9.3%
115Vac/60Hz 0.99 8.8%
230Vac/50Hz 0.97 12.4%
264Vac/50Hz 0.96 13.2%

 

2,1,2 Efficiency

 Table.3 Efficiency

Input Voltage 100% 75% 50% 25% Avg. Eff
115Vac/60Hz 90.0% 90.8% 90.2% 90.5% 90.37%
230Vac/50Hz 91.2% 90.5% 90.8% 90.5% 90.75%

2,2 Output Characteristics

2,2,1 Line Regulation @ Load Regulation

 Table.4 Line Regulation@l Load Regulation

Input Voltage No Load Half Load Full Load Specification
100Vac/60Hz 24.2V 24.1V 24.0V
115Vac/60Hz 24.2V 24.1V 24.0V
230Vac/50Hz 24.2V 24.1V 24.0V
264Vac/50Hz 24.2V 24.1V 24.0V
Line Regulation 0% 0.5%
Load Regulation 0.82% 1.5%

2,2,2 Ripple & Noise

 Table.5 Ripple & Noise

Input Voltage R&N (mV)
No Load Full Load Specification
100Vac/60Hz 23mV 87mV 100mV
115Vac/60Hz 23mV 72mV
230Vac/50Hz 22mV 46mV
264Vac/50Hz 22mV 46mV

2,2,3 Dynamic Test

The Dynamic Test with a low set at 10% load lasting for 10ms and high set at 100% load lasting for 10ms is added to the output. The ramp is set at 0.25A/us at transient.

 Table.6 Dynamic Test

Input Voltage
Output(mV) Specification
100Vac/60Hz
115Vac/60Hz
230Vac/50Hz
264Vac/50Hz

2,2,4 Time Sequence (Full load)

 Table.7 Time Sequence

Item Input voltage Meas.Data Specification
Set up time 230V/115V 73.6mS/340mS <500mS
Hold-up time 230V/115V 25.6mS/25.2mS >10mS
Rise Time 230V/115V 104.5mS/136.3ms <150mS
Fall Time 230V/115V 11.1mS/11.8mS  NA

2,3 Temperature Test

 Table.8 TemperatureTest

 The thermal test is under 30℃ ambiance after 4 hours full load runing with 230Vac input

Position Mark Description Value
BD1 P1 Bridge 64.7
Q1 P2 PFC MOS 65℃
Q2 P3 QR MOS 67.5℃
D1 P4 Didoe 66.1
T1 P5 PFC Transformer 50.3
CAP1 P6 Capacitor 51.1℃
T2 P7 QR Transformer 91℃
Q3 P8 Synchronous MOS 77
CAP2
P9 Capacitor 61.3
CAP3 P10 Capacitor 56.3

 

3, Protection Performance

3,1 Over Current Protection

Input Voltage OCP Trigger Current (A) Specification
100Vac/60Hz 5A 5A
115Vac/60Hz 5A
230Vac/50Hz 5.4A
264Vac/50Hz 5.4A

 3,2 Over Voltage Protection

Input Voltage Output OVP Trigger Voltage (V)
115Vac/60Hz 29.5V
230Vac/50Hz 29.3V